Power Panels – tabs

Our MDB and MCC Panels range up to 10,000A with short circuit levels up to 130kA IEC 61439 1-2 type and are tested with DEKRA up to 5,000A at 50°C ambient temperature.

Our distribution panels can be equipped with ACB, MCCB or MCB in fixed, plug-in and draw out versions. Our MCCs can be equipped with a wide variety of motor starters with the possibility of intelligent communication to the overall control system. 

[/vc_column_inner]
[/vc_row_inner]

FEATURES

MODULAR SYSTEM

An Absolute Modular form of construction favors high Flexibility and customized Integrated System Solutions possible.Being a completely modular system any configuration of Distribution Switchboards, Motor Control Centers, Control Switchboards is possible, with easy extensions, maintenance and assembly reducing the time factor and quick delivery.

Control gear System achieves the highest safety standards:
• Personal protection by arc control
• Assembly protection by arc barriers
• Thermographic inspection areas
• Mechanical safety interlocks
• IP20 internal protection

Personal & Product Safety

Unique Ventilation Ducts – To avoid any harmful injury to product and person our system provides unique independent explosion ventilation ducts, accessible to all functional units. These ducts allows the over pressure and ionized gases gathered due to some arc fault inside the chamber, escape out through the chimney provided on the top of switchboard.

Cladding system provides the most robust flexible system available:

• High strength 5 bend profile
• 2mm Aluzinc material
• Modular in 3 axes
• Doors in 1.5mm or 2.0mm
• IP44 standard(IP54 optional)
• Special colours available
• Customized cut-out’s

Unique Busbar System

The specially designed Bus bar System is capable of carry­ing current up to 8500A duly type tested to withstand a fault level up to 130 kA for 1 sec.The Bus bar System incorpo­rates a 2/3/4 bar per phase arrangement, both horizontal and vertical, eliminating time consuming work of drilling and bending the copper bars Internal Arc barriers are also available.

Versatile Internal Segregation

The modular system comes in FORM 1 to FORM 48 with different levels of segregation between the functional unit and the Busbar section depending on the type of applica­tion. The degree of safety increases with the choice of a higher FORM of Switchboards.

Spacious Cable Section 

The system provides enough space for cables which leads towards easy, effective and economic installation.

SPECIFICATIONS

Reference 
standards 
 Type-tested Switchgear and Controlgear Assembly IEC-61439-2/60439-1,
BS EN 60439-1/61439-1,2,
EN 60439-1/61439-1,2,IEC 60529,
IEC 62208, IEC/TR 61641,
CSA-C22.2 No.31 & 14,
DIN VDE 0660 part 500,DIN 43671/12.75, Ships Classification Societies
 Electrical Data       Rated Voltages Rated impulse withstand voltage(Uimp)                                        9.8 kV/8 kV
Rated insulation voltage(Ui)                                                             1000V
Rated operational voltage(Ue)                                                          690V
 Rated Currents    Main Busbar System, Horizontal & Vertical
Rated current(ln)                                                                                                8500A
Rated Peak withstand
current(lpk )                                                                                           300 kA
Rated Short-time withstand
current(lcw)                                                                                            130 kA 1 sec
Distribution Busbars, Fixed System
Rated current(ln)                                                                                   5500A
Rated Peak withstand
current(lpk )                                                                                            300 kA
Rated Short-time withstand
current(lcw)                                                                                             130 kA 1 sec
Distribution Busbars, Wlthdrawable & Removable System
Rated current(ln)                                                                                    1600A
Rated Peak withstand
current(lpk)                                                                                              105 kA
Rated Short-time withstand
current(lcw)                                                                                              50 kA 1 sec
Rated current(ln)                                                                                     2500A
Rated Peak withstand
current(lpk )                                                                                              105 kA 3 sec
Rated Short-time withstand
current(lcw)                                                                                               50 kA 3 sec
Mechanical
Data
 Internal Separation IEC 60439-1/61439-1                                                                              Form 1 to 4,A and B
BS EN 60439-1
 Degree of Protection  IEC 60529                                                                                                 Upto IP54
AdditionalFeatures Vibration Test IEC 439-1, (BS5486 VDE 0660), FORM 4, 660V
Bump Test IEC 439-1, (BS5486 VDE 0660), FORM 4, 660V